Drinking water quality · 2025
· Verified
What's in Saticoy Country Club-city of Ventura, CA tap water
27 contaminants were measured in the Saticoy Country Club-city of Ventura, CA water system's 2025 annual report. Each is shown below against its federal limit — 4 sit at or above that limit.
- Reporting year
- 2025
- Contaminants measured
- 27
- Over federal limit
- 4
- Approaching the limit
- 1
- Worst contaminant
- Total Dissolved Solids
- Service area
- CA
- Total Dissolved SolidsPhysical & aggregate · Average1240.875 MG/Llimit 1000 MG/L · 1.2× the limit
- SulfateInorganic chemicals · Average535.4166666666666 MG/Llimit 500 MG/L · 1.1× the limit
- SeleniumMetals · Average51.5 UG/Llimit 50 UG/L · 1.0× the limit
- Specific ConductancePhysical & aggregate · Average1604 UMHO/CMlimit 1600 UMHO/CM · 1.0× the limit
Where your water comes from · EPA SDWIS
Saticoy Country Club-city of Ventura, CA's drinking water comes from ground water, drawn from 2 sources.
Source
- SATICOY CC
- SATICOY CC WELL 02
Treatment
- SATICOT CC CLUB WELL 02 - CL2 TREATED
- WELL 03 CL2 TRT
Distribution
Historical readings · EPA Six-Year Review (2012–2019)
2 contaminants historically over EPA limits in Saticoy Country Club-city of Ventura, CA
Every U.S. public water system reports compliance-monitoring data to EPA. The Six-Year Review releases the 2012–2019 window as a single dataset — here's what your system reported, year by year. Values shown are the highest detection per analyte per year, compared to the federal MCL.
| Contaminant | Worst detection | EPA limit | Years (2012–2019) |
|---|---|---|---|
NITRATE worst: 2012 | 91.1 mg/L 9.1× | 10 mg/L | '12'13'14'15'16'17'18'19 |
NITRATE NITRITE worst: 2017 | 13.3 mg/L 1.3× | 10 mg/L | '16'17'18'19 |
SELENIUM worst: 2015 | 0.048 mg/L 96% | 0.05 mg/L | '12'13'14'15'17'18 |
TTHM worst: 2017 | 0.061 mg/L within | 0.08 mg/L | '12'13'14'15'16'17'18'19 |
ARSENIC worst: 2014 | 0.005 mg/L within below national p90 | 0.01 mg/L | '12'14'18 |
GROSS BETA worst: 2014 | 1.49 mrem/yr within | 4 mrem/yr | '14 |
FLUORIDE worst: 2017 | 0.92 mg/L within | 4 mg/L | '12'13'14'15'16'17'18'19 |
HAA5 worst: 2014 | 0.012 mg/L within | 0.06 mg/L | '12'13'14'15'16'17'18'19 |
PCE worst: 2014 | 0.0006 mg/L within | 0.005 mg/L | '14 |
BARIUM worst: 2012 | 0.0339 mg/L within below national p90 | 2 mg/L | '12 |
URANIUM worst: 2014 | 0.0173 ug/L within near national p90 | 30 ug/L | '12'13'14'17'18 |
COPPER worst: 2012 | 0.03 mg/L below national p90 | — | '12 |
LEAD worst: 2012 | 0.0031 mg/L | — | '12 |
DBAA worst: 2012 | 0.00656 mg/L | — | '12'13'14'15'16'17'18'19 |
DCAA worst: 2014 | 0.00133 mg/L | — | '14 |
MBAA worst: 2014 | 0.00137 mg/L | — | '14'17'19 |
MCAA worst: 2013 | 0.0011 mg/L | — | '13 |
TCAA worst: 2014 | 0.00216 mg/L | — | '14 |
BROMODICHLOROMETHANE worst: 2012 | 0.0039 mg/L | — | '12'13'14'15'16'17'18'19 |
BROMOFORM worst: 2012 | 0.0322 mg/L | — | '12'13'14'15'16'17'19 |
CHLOROFORM worst: 2012 | 0.0007 mg/L | — | '12'15'18 |
DIBROMOCHLOROMETHANE worst: 2012 | 0.0158 mg/L | — | '12'13'14'15'16'17'18'19 |
Physical & aggregate
| Contaminant | Measured | Federal limit | Status |
|---|---|---|---|
| Total Dissolved SolidsTotal dissolved solids — the combined content of all dissolved minerals and salts. | 1240.875 MG/LAverageSource water | 1000 MG/LMCL | At or above the limit |
| Specific ConductanceA measure of how well water conducts electricity, which tracks dissolved mineral content. | 1604 UMHO/CMAverageSource water | 1600 UMHO/CMMCL | At or above the limit |
| TurbidityA measure of cloudiness from suspended particles in the water. | 0.364 NTUAverageSource water | 5 NTUMCL | Within the limit |
| AlkalinityA measure of the water's capacity to neutralize acids. | 191.66666666666666 MG/LAverageDistribution | None set | Detected — no federal limit |
| pHA measure of how acidic or basic the water is. | 7.45 PHAverageDistribution | None set | Detected — no federal limit |
| TemperatureThe measured temperature of the water sample. | 21.2 CAverageDistribution | None set | Detected — no federal limit |
Inorganic chemicals
| Contaminant | Measured | Federal limit | Status |
|---|---|---|---|
| SulfateA naturally occurring mineral from rock and soil. | 535.4166666666666 MG/LAverageSource water | 500 MG/LMCL | At or above the limit |
Radionuclides
| Contaminant | Measured | Federal limit | Status |
|---|---|---|---|
| Gross AlphaGross alpha particle activity — a combined measure of alpha-emitting radioactive substances. | 14.875 PCI/LAverageSource water | 15 PCI/LMCL | Approaching the limit |
| Combined RadiumCombined radium-226 and radium-228 — naturally occurring radioactive elements. | 0.3143611111111111 PCI/LAverageSource water | 5 PCI/LMCL | Within the limit |
Metals
| Contaminant | Measured | Federal limit | Status |
|---|---|---|---|
| CalciumA naturally occurring mineral that contributes to water hardness. | Not detected MG/LHighest single sampleDistribution | None set | None detected |
VOCs & pesticides
| Contaminant | Measured | Federal limit | Status |
|---|---|---|---|
| 1,2,3-TCP | Not detected UG/LHighest single sampleSource water | 0.005 UG/LMCL | None detected |
People also ask about Saticoy Country Club-city of Ventura, CA's water
+Is Saticoy Country Club-city of Ventura, CA tap water safe to drink in 2025?
The 2025 Consumer Confidence Report for the Saticoy Country Club-city of Ventura, CA water utility lists 4 contaminants at or above the federal limit: Total Dissolved Solids, Sulfate, Selenium, and Specific Conductance. Whether that means the water is "unsafe" depends on which contaminant, how long the exposure, and individual health factors. The table on this page shows the measured value, the federal threshold, and the regulated statistic used for compliance.
+What contaminants are in Saticoy Country Club-city of Ventura, CA tap water?
27 contaminants were measured in Saticoy Country Club-city of Ventura, CA's 2025 Consumer Confidence Report, spanning disinfection byproducts, physical & aggregate, and other. 13 have an enforceable federal limit; the rest are detected but unregulated. Every measured value, in the utility's own units, is on this page.
+Which contaminants exceed federal limits in Saticoy Country Club-city of Ventura, CA tap water?
4 contaminants in Saticoy Country Club-city of Ventura, CA's 2025 report sit at or above the federal limit: Total Dissolved Solids (1.2× the limit); Sulfate (1.1× the limit); Selenium (1.0× the limit); Specific Conductance (1.0× the limit). The EPA enforces these limits against the regulated reporting statistic — typically a running annual average or 90th percentile — not a one-off sample spike.
+What is the worst contaminant in Saticoy Country Club-city of Ventura, CA tap water?
The contaminant with the highest measured value relative to its federal limit in the 2025 report is Total Dissolved Solids, at 1.2× the federal threshold. It belongs to the physical & aggregate family of contaminants.
+Are any contaminants in Saticoy Country Club-city of Ventura, CA tap water approaching the federal limit?
One contaminant is between 80% and 100% of the federal limit in this report: Gross Alpha. Approaching means measured but not in violation — a margin that can close quickly if conditions change.
+Where does the data on this page come from?
Every value is transcribed from Saticoy Country Club-city of Ventura, CA's 2025 Consumer Confidence Report — the annual drinking-water report every U.S. public water utility is required by federal law to publish. The original source document is archived and viewable on this site. A water-quality report covers an entire service area, not a single address.
+How often is Saticoy Country Club-city of Ventura, CA's water quality data updated?
Each U.S. public water utility publishes one Consumer Confidence Report per year, covering the prior calendar year's measurements. This page reflects the 2025 report; a new report will replace it once the utility publishes its next annual update.